Quantitative Control Approach for Wind Turbine Generators to Provide Fast Frequency Response with Guarantee of Rotor Security

Siqi Wang, Kevin Tomsovic
Dept. of Electrical Engineering and Computer Science
University of Tennessee
Knoxville, TN 37996
Email: swang31@utk.edu
Abstract

Wind generation is expected to reach substantially higher levels of penetration in the near future. With the converter interface, the rotor inertia of doubly-fed induction generator (DFIG) based wind turbine generator is effectively decoupled from the system, causing a reduction in inertial response. This can be compensated by enabling the DFIG to provide fast frequency response. This paper proposes a quantitative control approach for DFIG to deliver fast frequency response in the inertial response time scale. A supplementary power surge function is added to the active power reference of DFIG. The exact amount of power surge that is available from DFIG-based wind turbine is quantified based on estimation of maximum extractable energy. Moreover, the operational constraints such as rotor limits and converter over-load limit are considered at the same time. Thus, the proposed approach not only provides adequate inertial response but also ensures the rotor speed is kept within a specified operating range. Rotor safety is guaranteed without the need for an additional rotor speed protection scheme.

Active power control, DFIG, high wind penetration, inertial response, kinetic energy

I Introduction

In recent years, the installed capacity of wind power has grown significantly. One major concern of a high penetration of wind generation is the reduced inertia, which results in deterioration of inertial response. According to[1] and[2], Electric Reliability Council of Texas (ERCOT) and Western Interconnect (WECC) have both reported deficiency in inertial response due to an increase of converter interfaced wind resources. Conventionally, synchronous generators serve as the major contributor to provide inertial response. With more synchronous generators forced offline, the burden could be shifted to the wind turbine generators as well. In fact, the speed change of synchronous generators is usually limited to between 1.0 to 0.95 and only 9.75% of the kinetic energy can be drawn, but asynchronously coupled DFIG can allow its speed to drop from 1.0 to 0.7 , so the potential kinetic energy drawn from DFIG could be much greater than that from conventional generators [3].

To release the potential kinetic energy from DFIG, a general approach is to introduce a support function as a supplementary control loop, adding to the active power reference. The existing approach for DFIG to provide inertial response can be roughly divided into three categories characterized by the shape of the support function: response; response; and fixed trajectory response [4]. The work reported in [5] introduced an additional supplementary controller proportional to the derivative of system frequency to emulate the natural inertial response ( response). Similarly, the work in [6] modifies the supplementary control signal to be proportional to the frequency deviation to achieve a greater contribution from the wind turbines ( response). However, both and response are scenario-based, the response shape depends on the system frequency measurement and the control gains. Moreover, is sensitive to measurement error and noise [6]. The shape of the fixed trajectory is not determined by the frequency disturbance but is based on a power surge function. The power surge function can be various types, such as the kinetic discharge function shown in [3] and the temporary frequency control function (TFCF) shown in [7].

However, the following two questions remain open regarding the fixed trajectory response approach:

1) How to quantitatively design the power surge function to maximize a DFIG’s contribution without stalling the rotor?

2) How to coordinate multiple DFIGs under different operating conditions to provide fast and adequate system response?

This paper investigates these two questions and proposes a possible solution - a quantitative control approach for DFIG to provide fast frequency response with guaranteed rotor security. First, the maximum power injection for a given DFIG is identified based on wind turbine maximum extractable energy and the minimum allowable rotor speed. Then a coordination scheme is presented for DFIGs with different wind speed to deliver an adequate response.

The rest of the paper is organized as follows: Section II introduces the DFIG modeling approach and the control system. Section III presents the proposed control approach. Case studies are demonstrated on a 181-WECC system with 50% wind penetration in Section IV. Conclusions are given in Section V.

Ii DFIG Model and Control System

The objective of this paper is to study the large-scale power system frequency response, so the positive sequence type-3 DFIG machine model is adopted here. The generator is modeled as a controlled current source, while the decoupled active current and excitation current determine the required active and reactive power injection to the grid [8]. The basic DFIG-based wind turbine generator model are shown in Figure 1.

\includegraphics

[width=0.50height=0.23]Figs/WTG_Control_Basic.PNG

Figure 1: DFIG-based wind turbine generator model

Two first-order low-pass filters with a time constant of ms will represent the converter control systems [9]. This model has been validated and widely used in large-scale system wind integration studies in previous studies, such as, [6] and [10]. It is assumed that DFIGs within the same wind farm has the same wind speed and can be aggregated into a single unit with the same MVA rating as the summation of each DFIG’s MVA rating [6]. The wind speed spatial variation across regions is not the focus of this work, and thus, is neglected. A similar assumption can be found in [6] and [11]. The regular operation mode for DFIG is based on the widely used maximum power point tracking (MPPT) strategy. The active power reference of DFIG for a measured rotor speed is:

(1)

with

(2)

where is the air density, is the wind turbine swept area, is the wind turbine radius, is the power coefficient, is the pitch angle, is the tip speed ratio and is the wind speed [12].

The mechanical power extracted from a wind turbine can be expressed as :

(3)

The one-mass drive train model with wind turbine inertia is:

(4)

Iii Fast Frequency Response from DFIG with Consideration of Rotor Limits

During normal operation, DFIG still follows the power reference of MPPT as shown in (1). During frequency disturbances, the MPPT mode is bypassed, the support mode is activated to inject excess active power from wind turbine and the is added to the initial power reference . Due to fast response of converter control action, the electrical power output will quickly increase to , but turbine aerodynamic power will remain near . The mismatch will force rotor speed to decelerate and the stored kinetic energy will be released. With no reserve allocated, the DFIG on support mode is expected to only provide temporary frequency support, the active power output will finally return to maximum power point, and thus, the overall response should include a short over-production period and a recovery period to allow for rotor speed restoration as shown in Figure 3. In this work, we propose to calculate the exact amount of power injection based on estimated maximum deliverable energy , maximum rotor speed deviation and maximum converter overload limit .

Iii-a Estimation of Maximum Power Injection

From the energy point of view, the energy balance of DFIG in support mode can be expressed as follows [13]:

(5)

where is the aerodynamic energy variation, is the electric energy variation, is the energy losses, is the kinetic energy variation, is the total delivery time. Assuming wind speed is constant during a temporary power injection period:

(6)

Approximating as the first two terms of Taylor’s series yields [13]:

(7)

Further assuming the rate of rotor speed deviation is constant, while is constant, the partial derivative of the power coefficient in (7) can be approximated as:

(8)

Integrating (6), (7) and (8) over time yields:

(9)

The kinetic energy variation during the support period is:

(10)

and the electric energy variation is:

(11)

The energy loss variation can be approximated by mechanical losses as:

(12)

where is the energy efficient. Thus, combining (5), (9), (10), (11) and (12), the overall energy delivered during power injection period can be expressed as follows:

(13)

This expression reveals the relationship between the delivered energy , the rotor speed deviation and the delivery time . By specifying and allowable maximum rotor speed deviation , the maximum extracted energy and the corresponding power injection can be calculated.

Note when applying the calculated maximum power injection, the actual energy released by DFIG is smaller than calculated. As shown in Figure 3, the supplementary power reference is represented by the black curve, but the true response curve is shown in blue. The response reduces the rotor speed (the term in (1)), and thus, reduces the power reference and tapers off the ideal response[14]. A similar observation is obtained in Ref [14]. While the calculation is conservative, this can guarantee the rotor speed of DFIG always remains higher than the minimum allowable limit, and no additional rotor speed protection scheme is required.

A DFIG response example with 9.44 and minimum allowable rotor speed 0.7 is shown in Figure 3 to illustrate the conservative nature of the result.

\includegraphics [width=]Figs/Conservative.png
Figure 2: Illustrative example of conservatives
\includegraphics [width=]Figs/Conservative_realsimulation.PNG
Figure 3: DFIG response example

Another constraint that must be taken into consideration when calculating the maximum active power injection is the converter limit (here assumed to be p.u). Finally, the maximum power injection of a DFIG on support mode at a given wind speed can be expressed as:

(14)

where is the initial operating point of DFIG with wind speed . The can be saved as a look-up table and used as criteria for on-line selection of DFIGs for delivery of fast frequency response.

Iii-B Sensitivity Measure of Frequency Nadir to Active Power Change

The second step is to obtain the sensitivity measure of frequency nadir variation to active power injection change. Consider, the first order frequency response model shown in Figure 5, the frequency nadir of this system is given by [15]:

(15)

with

(16)

where is the base frequency, is the mechanical power gain factor, is the droop gain, is the damping coefficient. is the reheat time constant and is the fraction of total power generated by the HP turbine. The detailed explanation of (15) and (16) with the notations can be found in [16] which is not discussed in detail in this paper.

Equation (15) shows that the overall injected active power to the system has a near linear relationship with the system frequency nadir . A similar conclusion is reached in Ref [17], and is further verified by a detailed transient simulation result of a nonlinear power system in this paper as shown in Figure 5.

\includegraphics [width=]Figs/low_order_df.png
Figure 4: LFR model.
\includegraphics [width=]Figs/dP_df.png
Figure 5: varies with .

The above analysis indicates the sensitivity measure of frequency nadir to a real power change can be assessed by the matrix for all participating DFIGs with different wind speed using offline simulations. With the and the matrix , the minimum commitment of DFIGs to avoid excessive frequency excursions from to can be computed for each possible under-frequency event offline. During online operation, when detecting the under-frequency event, the scheduled minimum number of DFIGs on support mode will be initiated to ensure the frequency nadir will be above the specified threshold.

Iii-C Summary of the approach

The flow chart of the proposed approach is shown in Figure 6.

\includegraphics

[width=0.4height=0.3]Figs/offline_online.png

Figure 6: Flowchart of proposed control approach.

It is assumed that the short term wind speed prediction is available every 5 minutes. The sensitivity matrix and maximum power injection can be obtained and stored in a database. The minimum number of DFIGs on support mode that need to provide fast frequency response is scheduled at the beginning of each 5-minute interval. Once detecting a frequency deviation out of the specified dead-band, the on-line process activates the scheduled DFIGs. The power reference deviation is then calculated and added to the MPPT reference.

Iv Case Studies and Simulation Results

A DFIG based wind farm model is developed as a user-defined model in OpenModelica, and compiled as a functional mock-up unit (FMU) then linked to ePHASORsim, which is a real-time power system dynamic simulation software [18]. The proposed control approach is implemented on the 181-bus WECC system presented in [19] and modified to have 50% wind penetration. The wind locations are chosen based on NREL wind integration database which is available in [20]. The other synchronous units in the system were modeled with a round rotor machine (GENROU), AC exciter (IEEEX1), turbine governor (IEEEG1) and a power system stabilizer (IEE2ST). To represent the equivalent frequency of the system, a center of inertia (COI) reference frequency is used as the monitoring frequency for comparison of different scenarios [21].

In the first case study, the largest generator trip event (2160 MW) is evaluated for the studied system. As shown in Figure 7, the blue curve is the response of the studied system without wind penetration under this event, the purple curve is the frequency response to the same event with 50% wind penetration while all DFIGs are on MPPT with no contribution to frequency disturbance.

\includegraphics

[width=0.48height=0.24]Figs/NO_50P_WIND_F.png

Figure 7: Frequency response comparison.

Referring to (15) in the previous section, the replacement of the synchronous generators reduces the overall equivalent inertia constant, leads to a higher ROCOF, and causes the frequency nadir to decrease to 59.66 Hz from 59.81 Hz which is close to the under frequency load shedding limit (59.65 Hz). At the same time, the less effective governor response deteriorates the primary regulation capability, reducing the settling frequency from 59.94 Hz to 59.86 Hz.

Next, five DFIG units with wind speed ranging from 7 to 12 are scheduled to provide frequency support with the same system condition as previous. The matrix and for each wind speed are available in the database and are given in Table I.

Unit Number
DFIG unit 1 10.35 0.3347 0.1526
DFIG unit 2 9.83 0.2652 0.2089
DFIG unit 3 7.90 0.0754 0.1259
DFIG unit 4 11.00 0.4339 0.0686
DFIG unit 5 8.50 0.1221 0.2530
TABLE I: , under various

To ensure a 0.1 Hz security margin from the UFLS threshold, the frequency nadir threshold is set to be 59.75 Hz. Considering the same worst-case generator trip event as previous case study, when the DFIG nearby bus frequency is beyond the dead-band, the minimum number of DFIG units on support mode are switched in. The frequency response is shown in Figure 8.

\includegraphics

[width=0.46height = 0.26]Figs/TPI_multipleTdel.png

Figure 8: Frequency response comparison under MPPT and support mode

In this particular case, two units (DFIG unit 1 and DFIG unit 2 in Table I) are required to meet the 0.1 Hz frequency nadir improvement. Compared to the no control case (the black curve in Figure 8), the initial ROCOF is smaller and the initial frequency nadir is above the specified 59.75 Hz. It is also noticeable that there is a second frequency dip associated with the fact that the rotor speed of the DFIG needs to recover back to pre-disturbance speed. This can only be avoided if the DFIG is on reserve mode or compensated by other resources. Still, it can be improved by adjusting recovery time. Figure 8 also shows the frequency response with different recovery time. It can be seen that when increasing the recovery time, the frequency dip is reduced but the recovery time is prolonged. System planners must ensure that the manner in which energy is delivered and recovered is optimal for the specific system [4].

Figure 9 shows the active power contribution of each DFIG unit, which indicates the maximum power injection of each DFIG unit follows the schedule. The rotor speed response for each DFIG unit is shown in Figure 10, and verifies that the rotor speed remains above the minimum allowable limit.

\includegraphics

[width=0.48height = 0.24]Figs/Pe_all_multipleTrec.PNG

Figure 9: Active power of scheduled DFIGs under support mode.
\includegraphics

[width=0.48height = 0.24]Figs/wr_all_multipleTrec.PNG

Figure 10: Rotor speed of DFIGs under support mode.

V Conclusion

This paper presents a quantitative control approach for DFIG to provide fast frequency response by incorporating a supplementary power surge function to the existing MPPT reference. The supplementary power surge amount is carefully designed considering maximum active power injection capability of each DFIG and the converter overload limits. As demonstrated by the simulation results, the proposed approach not only improves the overall frequency response but also ensures the rotor speed is kept within a safe range. Rotor limits can be maintained without additional actuator for rotor speed protection.

References

  • [1] J. Conto. Grid challenges on high penetration levels of wind power. In Proc. IEEE Power Energy Soc. Gen. Meeting (PES GM), pages 1–3, July 2012.
  • [2] S. H. Huang, D. Maggio, K. McIntyre, V. Betanabhatla, J. Dumas, and J. Adams. Impact of wind generation on system operations in the deregulated environment: ERCOT experience. In Proc. IEEE Power Energy Soc. Gen. Meeting (PES GM), pages 1–8, July 2009.
  • [3] P. K. Keung, P. Li, H. Banakar, and B. T. Ooi. Kinetic energy of wind-turbine generators for system frequency support. IEEE Trans. Power Syst., 24(1):279–287, 2009.
  • [4] L. Ruttledge and D. Flynn. Emulated inertial response from wind turbines: gain scheduling and resource coordination. IEEE Trans. Power Syst., 31(5):3747–3755, Sept 2016.
  • [5] J. Ekanayake and N. Jenkins. Comparison of the response of doubly fed and fixed-speed induction generator wind turbines to changes in network frequency. IEEE Trans. Energy Convers., 19(4):800–802, Dec 2004.
  • [6] D. Gautam, L. Goel, R. Ayyanar, V. Vittal, and T. Harbour. Control strategy to mitigate the impact of reduced inertia due to doubly fed induction generators on large power systems. IEEE Trans. Power Syst., 26(1):214–224, Feb 2011.
  • [7] N. R. Ullah, T. Thiringer, and D. Karlsson. Temporary primary frequency control support by variable speed wind turbines - potential and applications. IEEE Trans. Power Syst., 23(2):601–612, May 2008.
  • [8] I. A. Hiskens. Dynamics of type-3 wind turbine generator models. IEEE Trans. on Power Syst., 27(1):465–474, Feb 2012.
  • [9] L. R. Chang-Chien, C. C. Sun, and Y. J. Yeh. Modeling of wind farm participation in AGC. IEEE Trans. Power Syst., 29(3):1204–1211, May 2014.
  • [10] M. H. Variani, S. Wang, and K. Tomsovic. Study of flatness-based automatic generation control approach on an NPCC system model. In Proc. IEEE Power Energy Soc. Gen. Meeting (PES GM), pages 1–5, July 2015.
  • [11] F. Wilches-Bernal, J. H. Chow, and J. J. Sanchez-Gasca. A fundamental study of applying wind turbines for power system frequency control. IEEE Trans. Power Syst., 31(2):1496–1505, Mar 2016.
  • [12] H. Pulgar-Painemal. Wind Farm Model for Power System Stability Analysis. Phd dissertation, University of Illinois at Urbana-Champaign, 2010.
  • [13] G. C. Tarnowski. Coordinated Frequency Control of Wind Turbines in Power Systems with High Wind Power Penetration. PhD thesis, Technical University of Denmark, 2012.
  • [14] L. Wu and D. G. Infield. Towards an assessment of power system frequency support from wind plant - modeling aggregate inertial response. IEEE Trans. on Power Syst., 28(3):2283–2291, Aug 2013.
  • [15] Q. Shi, H. Cui, F. Li, Y. Liu, W. Ju, and Y. Sun. A hybrid dynamic demand control strategy for power system frequency regulation. CSEE J.Power Energy Syst., 3(2):176–185, June 2017.
  • [16] P. M. Anderson and M. Mirheydar. A low-order system frequency response model. IEEE Trans. Power Syst., 5(3):720–729, Aug 1990.
  • [17] R. Bhana and T. J. Overbye. The commitment of interruptible load to ensure adequate system primary frequency response. IEEE Trans. Power Syst., 31(3):2055–2063, 2016.
  • [18] V. Jalili-Marandi, F. J. Ayres, E. Ghahremani, J. Bélanger, and V. Lapointe. A real-time dynamic simulation tool for transmission and distribution power systems. In Proc. IEEE Power Energy Soc. Gen. Meeting (PES GM), pages 1–5, July 2013.
  • [19] S. Maslennikov, B. Wang, Q. Zhang, a. Ma, a. Luo, a. Sun, and E. Litvinov. A test cases library for methods locating the sources of sustained oscillations. In Proc. IEEE Power Energy Soc. Gen. Meeting (PES GM), pages 1–5, July 2016.
  • [20] C. Draxl, A. Clifton, B.-M. Hodge, and J. McCaa. The wind integration national dataset (wind) toolkit. Applied Energy, 151:355 – 366, 2015.
  • [21] H. Pulgar-Painemal, Y. Wang, and H. Silva-Saravia. On inertia distribution, inter-area oscillations and location of electronically-interfaced resources. IEEE Trans. on Power Syst., PP(99):1–1, 2017.
Comments 0
Request Comment
You are adding the first comment!
How to quickly get a good reply:
  • Give credit where it’s due by listing out the positive aspects of a paper before getting into which changes should be made.
  • Be specific in your critique, and provide supporting evidence with appropriate references to substantiate general statements.
  • Your comment should inspire ideas to flow and help the author improves the paper.

The better we are at sharing our knowledge with each other, the faster we move forward.
""
The feedback must be of minimum 40 characters and the title a minimum of 5 characters
   
Add comment
Cancel
Loading ...
165681
This is a comment super asjknd jkasnjk adsnkj
Upvote
Downvote
""
The feedback must be of minumum 40 characters
The feedback must be of minumum 40 characters
Submit
Cancel

You are asking your first question!
How to quickly get a good answer:
  • Keep your question short and to the point
  • Check for grammar or spelling errors.
  • Phrase it like a question
Test
Test description