Impact of Distributed Energy Resources on Frequency Regulation of the Bulk Power System

Impact of Distributed Energy Resources on Frequency Regulation of the Bulk Power System

Mohammad Khatibi and Sara Ahmed
Department of Electrical and Computer Engineering
University of Texas at San Antonio
San Antonio, TX
Mohammad.Khatibi@utsa.edu
Abstract

The growing penetration of distributed energy resources (DERs) has increased the complexity of the power system due to their intermittent characteristics and lower inertial response, such as photo voltaic (PV) systems and wind turbines. This restructuring of power system has considerable effect on transient response of the system resulting in inter area oscillations, less synchronized coupling and power swings. Furthermore the concept of being distributed itself and generating electricity from multiple locations in power system makes the transient impact of DERs even worse by raising issues such as reverse power flows. This paper studies some impacts of the changing nature of power system which are limiting the large scale integration of DERs. In addition a solution to increase the inertial response of the system is addressed by adding virtual inertia to the inverter based DERs in power system.The proposed control results in increasing the stability margin and tracking the rated frequency of the system. The injected synchronized active power to the system will prevent the protection relays from tripping by improving the rate of change of frequency. The proposed system operation is implemented on a sample power grid comprising of generation, transmission and distribution and results are verified experimentally through the Opal-RT real-time simulation system.

power system stability,distributed energy resources, photo voltaic system, virtual inertia, rate of change of frequency.

I Introduction

[1]In recent years, significant inverter-based inertia-less renewable generation has been integrated in both bulk transmission and distribution (T&D) power systems to improve the sustainability of electric power systems. The increasing penetration of the distributed energy resources (DERs) displacing conventional synchronous generators (SGs) is rapidly changing the dynamics of the large-scale power systems. The electric grids lose inertia, voltage support and oscillation damping. When majority of generated electricity is coming from synchronous generators working with fossil fuels, using DERs reduces the system fuel costs significantly but can have considerable impact on system reliability. This less reliable grid pushed the power system planners to develop a method that helps to decide on operating policies, mixes and sizes in capacity expansion and installation sites when utilizing wind and photo voltaic (PV) systems [2]. Network expansion planning, voltage stability studies and coordination of voltage controls at the T&D interface are investigated through power flow which is from transmission to distribution in traditional power grids. Reverse power flow from DGs to transmission system and impact of DERs on voltage stability in restructured power grids with high penetration of DERs asks for a new modeling and representation for DGs. For example in [3, 4] only positive sequence representation has been considered for power flow analysis in presence of DERs which is not enough for an unbalanced distribution grid with unbalanced laterals. in [3] a three-phase power-flow algorithm is proposed which includes unbalanced lines and loads, single phase laterals and three/four wire distribution lines. A detailed analysis of the impact of large scale wind power generation on the dynamic voltage stability and the transient stability of electric power systems is presented in [5]. Using a multidimensional parameter variation [6] shows that different control strategies of renewable energy sources have a significant influence on voltage stability of the power system. To verify the relay protection settings and operation and circuit breaker and fuse ratings, short circuit analysis should to be taken in into account. The dynamics of DERs should be included in short circuit analysis during fault in distribution system since each DER will contribute to short circuit current.

Inverter based DGs has no inertia. To solve this problem the idea of virtual synchronous machine/ generator (VSM/VSG) has been presented in [7, 8] in which the power electronics interface (PEI) is mimicking the behavior of the SGs. However the implementation of virtual inertia in the literature varies based on the desired level of of model complexity and aplication, the underlying concept is similar among various topologies. Using a detailed mathematical model which represents the dynamics of SG or simpifying the model by using only the swing equation are the the two main solutions for implementing virtual inertia [7, 9]. For example to represent the same dynamics as SGs, synchroverters are introduced in [10] for inverter-based DGs. Hence as an advantage, traditional operation of power system can be continued without significant canges in operation structure [11]. Similar to synchroverter approach, Ise lab is another topology in literaure to implement virtual inertia. In this method, the contro loop solve the swing equation in each cycle to emulate inertia, instead of using a full detail model of SG [12]. Other than different topologies VSG application has been illuterated extensively in the literature. In [13] an enhanced VSG control is proposed in which by adjusting the virtual stator reactance, active power oscillations during transient states is improved. Furturmore, using inverse voltage droop control and ac bus voltage estimation, an accurate reactive power sharing is achieved. In [14], the dynamic characteristic of simple droop control and VSG are studied through deriving small signal equations in both islanded and grid connected mode. Then the proposed inertial droop control by the author, inherits the advantage of droop and provides inertial support for the system. Voltage angle deviations (VADs) of generators with respect to the angle of the center of inertia are defined in [15] as a tool for transient stability assessment of the multi-VSG micro-grid. To have a smooth transition during disturbances and keeping VADs within a specific range, VSG parameters are tuned using particle swarm optimization. In [16] the detailed parameter designs of VSG is proposed and also the conditions to decouple active and reactive power loops are given. For avoiding VSG output voltage distortions the author indicates indicates that the bandwidth of the power loop should be very smaller than twice the line frequency In [17] to enhance the inertial response of DC micro-grids and stabilize the DC bus voltage fluctuations, the author proposed virtual inertia strategy for DC micro-grids through bidirectional grid-connected converters. A fuzzy-secondary-controller-based VSG control scheme is proposed in [18] for voltage and frequency regulation in micro-grids. [19] proposed a low voltage ride through control strategy for VSG control scheme with providing reactive power support under grid fault. The solution strategy for VSG working under unbalanced voltage conditions is discussed in [20]. A new VSG control in presented in [21] with capability to avoid harmonic interference and accurate control vector orientation process.

This paper is organized as follows. Section II introduces the proposed power grid with DERs. Section III discusses impacts of DERs on frequency while the solution for this impact is discussed in Section IV. Finally, simulation and experimental results and conclusion are shown in and Section V and Section VI receptively.

Fig. 1: Multiple time-frame frequency response in a power system following a frequency event.
Fig. 2: T&D combined system with VSG technologies.
Fig. 3: General schematic representation of the proposed VSG controller.

Ii transmission and distribution system

Fig. 2 shows the sample power grid with generation, transmission and distribution system. The Kundur’s two-Area system with parameters taken from [22] which is comprised of four synchronous generators(two in each area) that are boosting up with transformers and connected through transmission lines, form generation and transmission parts in this example. The areas are connected to each other through a tie line. IEEE 13 node test feeder [23] is used as distribution system. The DGs such as PV and battery energy storage unit (BES) are connected to distribution system using a voltage source inverter (VSI).

PV system includes PV arrays and a unidirectional boost DC-DC converter which is working under perturb and observe (P&O) maximum power point tracking (MPPT) control . BES includes batteries and a bidirectional boost DC-DC converter controlled by multi-loop voltage and current control. The outer loop controls voltage and inner loop controls current through proportional integral (PI) controllers. The BES and PV unit are connected in parallel and form the DC link.

Iii impact of der on frequency

Since the power electronic interfaces used in DGs has no rotating mass and damping, the inertial constant in the micro-grid is reduced which results in an increase in the rate of change of frequency (ROCOF) and may lead to load shedding even under small disturbances in the system. Fig. 1 shows the frequency curve of system with different amount of inertia in presence of a contingency. For the control and stability of these small scale power grids, a hierarchical control including primary, secondary and tertiary control is introduced, similar to conventional grids. Droop control for voltage source inverters as an example for primary frequency control is discussed in [24], provide barely any inertia/damping support for the grid.

Iv VSG control

Without any mechanical rotational part, inverters have a high response speed compared to the conventional rotational machines [25]. Virtual inertia concept is introduced as a solution to overcome this limitation [26]. By emulating the mechanical equation of a real synchronous generator into the inverter, similar behavior can be assumed during normal operation of the system and frequency disturbances for example the time that there is a sudden change (increase or decrease) in active power. Utilizing VSG algorithm, synchronized active power can be injected from the PV to the grid to stabilize the frequency [27, 28]. In this paper, during normal operation of the system (rated frequency and voltage), the perturb and observe method (P&O) sets the active power reference by measuring voltage and current of the PV [29]. This active power is controlled in two stages as shown in Fig. 4. At the first stage, primary frequency is implemented in the same way as a SG. In the second stage virtual inertia and damping are added to complete the loop. The result is a reference angle that will be fed into park transform [30].
VSG control can be divided into two sections. First, the mechanical swing equation needs to be emulated and solved numerically. Then the results are used as a reference to control the voltage and current of the inverter.

Fig. 4: General schematic representation of the proposed VSG controller.

Iv-a P-F control

Mechanical equation of a SG assuming that the rotor is a rigid body can be described as

(1)

where is the inertia constant in p.u. derived from (2), is the base power of the machine, is the angular frequency of the SG and the rated angular frequency [31].

(2)

and are the mechanical output torques of the prime mover and the electromagnetic torque of the SG respectively and can be calculated using (3) :

(3)

in which is the rated active power and is the output power of the DG. The primary frequency control method and damping coefficient are working here as in the similar to a real SG and are achieved through a proportional cycle in which is the droop coefficient and is called the damping coefficient. for typical synchronous machines varies between 2 and 10 s [32]. The VSG response at a specific output power and voltage is determined by parameters of its second order differential equation which are the real part of its eigenvalues and the damping ratio .These parameters are related to and directly through the following equation set

(4)

where is the maximum transferable power from the VSG bus to the grid, is the voltage angle of the VSG with respect to the grid and is the undamped natural frequency of the VSG. At any working conditions, the parameters corresponding to the desired system response can be achieved by tuning and [33].

Iv-B Q-E regulation

controlling voltage is achieved by regulating the reactive power as (5)

(5)

where is the reference voltage, is reactive power droop coefficient and is the nominated voltage amplitude.

Iv-C V/I control

This control loop features a conventional outer voltage and inner current loop. Its primary function is regulating the output voltage with no steady state error while quickening the dynamic response of the current loop to strengthen the ability of inverter control. This can be achieved through the outer voltage and inner current control loop. The calculated reference voltage using (5) is set as the reference for the outer voltage loop. Since the control is achieved in constant reference frame, is transformed from synchronous to dq reference frame using Park transformation given in (7) with the calculated angle in (1) as the input angle for the transformation. Then a PI controller is tuned to track the reference voltage and current.

(6)
(7)

The current of the converter is also controlled similarly using an inner PI controller.

V Simulations and results

As illustrated in Fig. 3, the proposed VSG is tested for different case studies such as normal condition and sudden changes in loads. The converter and control is simulated using Matlab/Simulink SimPowerSystems toolbox. Real time results are achieved using Opal Rt OP5600 and OP5607 Virtex7 FPGA simulator which is shown in Fig. 5. The converter switches are simulate in FPGA due to its capability of working with smaller sampling time with . The rest of simulation are implemented in simulator target with . The sampling time for both the simulator and FPGA is chosen based on their desired performance and also complexity of the control scheme.

Fig. 5: Opal RT simulator.

V-a Frequency Regulation

First the system is working under normal operation condition. The generated power by PV under MPPT is used to feed the load at the distribution system and rest of that is sent to the grid to feed the grid loads. At this scenario, the frequency behavior of the system is tested under different inertia constants () with 0.2 p.u increase in active load at in which the total load is still less than the total generated MPPT power. The frequency nadir is shown and compared in Fig. 6. The smaller inertia constant , the bigger frequency nadir and the deepest nadir is expected for the case when there is no inertia in system. The bigger frequency nadir results in a higher risk for the system that can cause it to disconnect from the main grid due to triggering ROCOF relays. In next scenario, the increase in load is equal to the total generation of the PV.
In Fig. 7 the system frequency performance is compared with the addition of DER and state-of-the-art power electronics inverters that doesn’t emulate inertia versus DERs with the proposed VSG control. The results shows the frequency nadir decreased with the addition of the virtual inertia. Fig. 8 depicts the system frequency response corresponding to the different DER penetration levels. It can be seen that the VSG is emulating the generator inertia and therefore even with a big increase in the DER penetration level, the frequency nadir is almost the same as with the generators only.

Fig. 6: Frequency deviation of the proposed system under different value of and 0.2 p.u. step load.
Fig. 7: System frequency with no DER, with DER and no inertia emulation and with DER and inertia emulation respectively at 200MW.
Fig. 8: Effect of DER with VSG on BES frequency.

Vi conclusion

DERs have multiple negative impacts on the bulk power systems which have been addressed in the paper. In between, lower or zero inertia is one of their major aspects that will affect the stability of the whole power grid and may lead into unwanted load shedding. The solution for adding inertia to DERs by mimicking synchronous generation behavior is introduced. By using the proposed seamless control framework, a simple control strategy is implemented to operate under normal and faulty grid conditions. Several experiments have been conducted to verify the performance of the proposed system.

Acknowledgments

This project was funded in-part by the University of Texas at San Antonio, Office of the Vice President for Research.

References

  • [1] Y. Fang, H. Zou, and Q. Huang, “Small-sized loudspeaker equalization based svd-krylov model reduction and virtual bass enhancement,” 2017.
  • [2] R. Karki and R. Billinton, “Reliability/cost implications of pv and wind energy utilization in small isolated power systems,” IEEE Transactions on Energy Conversion, vol. 16, no. 4, pp. 368–373, 2001.
  • [3] H. Nikkhajoei and R. Iravani, “Steady-state model and power flow analysis of electronically-coupled distributed resource units,” IEEE Transactions on Power Delivery, vol. 22, no. 1, pp. 721–728, 2006.
  • [4] H. Chen, J. Chen, D. Shi, and X. Duan, “Power flow study and voltage stability analysis for distribution systems with distributed generation,” in 2006 IEEE Power Engineering Society General Meeting.   IEEE, 2006, pp. 8–pp.
  • [5] J. Slootweg and W. Kling, “The impact of large scale wind power generation on power system oscillations,” Electric Power Systems Research, vol. 67, no. 1, pp. 9–20, 2003.
  • [6] S. Dierkes, F. Bennewitz, M. Maercks, L. Verheggen, and A. Moser, “Impact of distributed reactive power control of renewable energy sources in smart grids on voltage stability of the power system,” in 2014 Electric Power Quality and Supply Reliability Conference (PQ).   IEEE, 2014, pp. 119–126.
  • [7] U. Tamrakar, D. Shrestha, M. Maharjan, B. Bhattarai, T. Hansen, and R. Tonkoski, “Virtual inertia: Current trends and future directions,” Applied Sciences, vol. 7, no. 7, p. 654, 2017.
  • [8] H. Bevrani, T. Ise, and Y. Miura, “Virtual synchronous generators: A survey and new perspectives,” International Journal of Electrical Power & Energy Systems, vol. 54, pp. 244–254, 2014.
  • [9] A. Vassilakis, P. Kotsampopoulos, N. Hatziargyriou, and V. Karapanos, “A battery energy storage based virtual synchronous generator,” in 2013 IREP Symposium Bulk Power System Dynamics and Control-IX Optimization, Security and Control of the Emerging Power Grid.   IEEE, 2013, pp. 1–6.
  • [10] Q.-C. Zhong and G. Weiss, “Synchronverters: Inverters that mimic synchronous generators,” IEEE Transactions on industrial electronics, vol. 58, no. 4, pp. 1259–1267, 2010.
  • [11] Q.-C. Zhong, “Virtual synchronous machines: A unified interface for grid integration,” IEEE Power Electronics Magazine, vol. 3, no. 4, pp. 18–27, 2016.
  • [12] K. Sakimoto, Y. Miura, and T. Ise, “Stabilization of a power system with a distributed generator by a virtual synchronous generator function,” in 8th International Conference on Power Electronics-ECCE Asia.   IEEE, 2011, pp. 1498–1505.
  • [13] J. Liu, Y. Miura, H. Bevrani, and T. Ise, “Enhanced virtual synchronous generator control for parallel inverters in microgrids,” IEEE Transactions on Smart Grid, vol. 8, no. 5, pp. 2268–2277, 2016.
  • [14] J. Liu, Y. Miura, and T. Ise, “Comparison of dynamic characteristics between virtual synchronous generator and droop control in inverter-based distributed generators,” IEEE Transactions on Power Electronics, vol. 31, no. 5, pp. 3600–3611, 2015.
  • [15] J. Alipoor, Y. Miura, and T. Ise, “Stability assessment and optimization methods for microgrid with multiple vsg units,” IEEE Transactions on Smart Grid, vol. 9, no. 2, pp. 1462–1471, 2016.
  • [16] H. Wu, X. Ruan, D. Yang, X. Chen, W. Zhao, Z. Lv, and Q.-C. Zhong, “Small-signal modeling and parameters design for virtual synchronous generators,” IEEE Transactions on Industrial Electronics, vol. 63, no. 7, pp. 4292–4303, 2016.
  • [17] W. Wu, Y. Chen, A. Luo, L. Zhou, X. Zhou, L. Yang, Y. Dong, and J. M. Guerrero, “A virtual inertia control strategy for dc microgrids analogized with virtual synchronous machines,” IEEE Transactions on Industrial Electronics, vol. 64, no. 7, pp. 6005–6016, 2016.
  • [18] C. Andalib-Bin-Karim, X. Liang, and H. Zhang, “Fuzzy-secondary-controller-based virtual synchronous generator control scheme for interfacing inverters of renewable distributed generation in microgrids,” IEEE Transactions on Industry Applications, vol. 54, no. 2, pp. 1047–1061, 2018.
  • [19] K. Shi, W. Song, P. Xu, R. Liu, Z. Fang, and Y. Ji, “Low-voltage ride-through control strategy for a virtual synchronous generator based on smooth switching,” IEEE Access, vol. 6, pp. 2703–2711, 2017.
  • [20] T. Zheng, L. Chen, Y. Guo, and S. Mei, “Comprehensive control strategy of virtual synchronous generator under unbalanced voltage conditions,” IET Generation, Transmission & Distribution, vol. 12, no. 7, pp. 1621–1630, 2017.
  • [21] H. Zhao, Q. Yang, and H. Zeng, “Multi-loop virtual synchronous generator control of inverter-based dgs under microgrid dynamics,” IET Generation, Transmission & Distribution, vol. 11, no. 3, pp. 795–803, 2017.
  • [22] P. Kundur, N. J. Balu, and M. G. Lauby, Power system stability and control.   McGraw-hill New York, 1994, vol. 7.
  • [23] W. H. Kersting, “Radial distribution test feeders,” IEEE Transactions on Power Systems, vol. 6, no. 3, pp. 975–985, 1991.
  • [24] J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodriguez, “Control of power converters in ac microgrids,” IEEE transactions on power electronics, vol. 27, no. 11, pp. 4734–4749, 2012.
  • [25] J. Alipoor, Y. Miura, and T. Ise, “Distributed generation grid integration using virtual synchronous generator with adoptive virtual inertia,” in 2013 IEEE Energy Conversion Congress and Exposition.   IEEE, 2013, pp. 4546–4552.
  • [26] T. Shintai, Y. Miura, and T. Ise, “Oscillation damping of a distributed generator using a virtual synchronous generator,” IEEE transactions on power delivery, vol. 29, no. 2, pp. 668–676, 2014.
  • [27] A. Fathi, Q. Shafiee, and H. Bevrani, “Robust frequency control of microgrids using an extended virtual synchronous generator,” IEEE Transactions on Power Systems, vol. 33, no. 6, pp. 6289–6297, 2018.
  • [28] K. Sakimoto, Y. Miura, and T. Ise, “Stabilization of a power system including inverter type distributed generators by the virtual synchronous generator,” IEEJ Transactions on Power and Energy, vol. 132, pp. 341–349, 2012.
  • [29] X. Zhang, D.-b. ZHU, and H.-z. XU, “Review of virtual synchronous generator technology in distributed generation [j],” Journal of Power Supply, vol. 3, pp. 1–6, 2012.
  • [30] Y. Du, J. M. Guerrero, L. Chang, J. Su, and M. Mao, “Modeling, analysis, and design of a frequency-droop-based virtual synchronous generator for microgrid applications,” in 2013 IEEE ECCE Asia Downunder.   IEEE, 2013, pp. 643–649.
  • [31] Z. Zeng, W. Shao, L. Ran, Z. Lyu, and R. Li, “Mathematical model and strategic energy storage selection of virtual synchronous generators,” Automation of Electric Power Systems, vol. 39, no. 13, pp. 22–31, 2015.
  • [32] Y. Hirase, K. Sugimoto, K. Sakimoto, and T. Ise, “Analysis of resonance in microgrids and effects of system frequency stabilization using a virtual synchronous generator,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 4, no. 4, pp. 1287–1298, 2016.
  • [33] C. Li, J. Xu, and C. Zhao, “A coherency-based equivalence method for mmc inverters using virtual synchronous generator control,” IEEE Transactions on Power Delivery, vol. 31, no. 3, pp. 1369–1378, 2015.
Comments 0
Request Comment
You are adding the first comment!
How to quickly get a good reply:
  • Give credit where it’s due by listing out the positive aspects of a paper before getting into which changes should be made.
  • Be specific in your critique, and provide supporting evidence with appropriate references to substantiate general statements.
  • Your comment should inspire ideas to flow and help the author improves the paper.

The better we are at sharing our knowledge with each other, the faster we move forward.
""
The feedback must be of minimum 40 characters and the title a minimum of 5 characters
   
Add comment
Cancel
Loading ...
379835
This is a comment super asjknd jkasnjk adsnkj
Upvote
Downvote
""
The feedback must be of minumum 40 characters
The feedback must be of minumum 40 characters
Submit
Cancel

You are asking your first question!
How to quickly get a good answer:
  • Keep your question short and to the point
  • Check for grammar or spelling errors.
  • Phrase it like a question
Test
Test description